Overview
For certain multi-occupied residential buildings in England, the Fire Safety (England) Regulations 2022 introduce explicit expectations around fire door checks (particularly in common parts and flat entrance doors).
This article is a practical summary for property teams. Requirements vary by building type/height and must be aligned to your fire risk assessment.
For the official guidance, see GOV.UK:
Who these checks typically apply to
The regulations apply to multi-occupied residential buildings in England (e.g. blocks of flats) and introduce extra duties for higher buildings.
In practice, the fire door check expectations most teams care about are for buildings over 11 metres (and additional requirements apply for buildings over 18 metres / 7+ storeys).
If you manage mixed portfolios, treat this as a starting point:
- Always confirm the building type, height threshold, and who the Responsible Person is.
- Align any programme with the building’s fire risk assessment (FRA) and competent advice.
What the regulations mean for fire doors (in plain terms)
For many buildings over 11m the expectation is:
- Quarterly checks of fire doors in common parts (including self-closing devices).
- Annual checks of flat entrance doors that open onto common parts, using best endeavours (i.e. you may need to evidence attempts where access isn’t gained).
The point isn’t to create paperwork. The point is to keep doors performing the way they were intended: close, latch, and resist fire/smoke spread.
What this means operationally
Even if you already have a fire door programme, the “new” work is usually:
- being consistent about who checks what, and when
- keeping a clear audit trail (what was checked, what was found, what was fixed)
- having a repeatable process for access issues (e.g., flat entrance doors)
What to check during a door check
You can split checks into two layers:
-
Routine checks (fast, repeatable) to spot obvious failures.
-
Competent inspections (deeper) when defects are found, when programmes are planned, or when you need door-by-door condition survey outputs.
Here’s a routine checklist that works for most common-part doors:
- Does it close and latch from any open position (not just the last 50mm)?
- Self-closer present, fixed firmly, not leaking, not “disconnected”.
- Gaps broadly consistent and not obviously excessive.
- Seals present (smoke / intumescent where applicable), continuous and not painted over or missing.
- Hinges/ironmongery secure and not visibly failing.
- Door leaf and frame not damaged, warped, or heavily altered.
- Vision panel/glazing intact (if present) and beads appear secure.
- Signage present where required and not preventing closure.
- No wedges/hold-open misuse (and if hold-open devices exist, confirm they’re appropriate and functional).
For flat entrance doors, the same principles apply, with extra emphasis on:
- the self-closing device (where present/required)
- damage that compromises fit within the frame
- evidence of tampering or resident modifications
How it works
- Build/confirm a door register — each door has an ID and location (block / level / core / riser / etc.).
- Set the frequency — quarterly common parts checks; annual flat entrance checks where applicable.
- Run the checks — capture issues consistently (a simple defect code list helps).
- Prioritise defects — urgent life-safety issues separated from planned remedials.
- Close out — record what was fixed, what’s outstanding, and why.
What good evidence looks like
You don’t need 100-page reports for every visit, but you do need records that are easy to defend:
- asset list / register (door locations and IDs)
- date of inspection and areas covered
- defects captured clearly (with photos where helpful)
- prioritised next actions
- close-out notes once remedials are completed
If you want a simple, audit-friendly structure, record each check like this:
- Building / block
- Date / time
- Checker name + competence statement (internal process)
- Door ID / location
- Result (pass / fail / access not gained)
- Defects (plain English + photos where helpful)
- Priority (urgent / planned / monitor)
- Action owner (who will fix) + target date
- Close-out (date fixed + what was done)
A simple evidence table (one row per door)
| Field | Example | Why it matters |
|---|---|---|
| Door ID | CP-STAIR-A-L2-03 | Lets you re-check the same door next quarter |
| Location | Block A / Level 2 / Stair core | Stops ambiguity across cores |
| Check type | Quarterly common parts | Shows cadence and compliance intent |
| Outcome | Pass / Fail | Clear programme status |
| Defects | “Won’t latch” / “Seal missing” | Ties work to a reason |
| Priority | Urgent / Planned / Monitor | Helps triage and governance |
| Owner + target date | M&E contractor / 2026-02-10 | Makes defects actionable |
| Close-out | Closed 2026-02-12 | Shows risk reduction over time |
Common reasons programmes fail
- No IDs: “Door by the stairs” isn’t good enough in a multi-core building.
- Defects logged but not tracked: spreadsheets grow, risks remain.
- Over-reliance on one-off surveys: a door programme needs repeat cadence.
- Access planning ignored: annual flat checks require a process (letters, appointments, evidence of attempts).
FAQs
Do we need a specialist for quarterly checks?
Not always. Routine checks can be done by a competent person with a clear checklist. Where defects are found, or where you need a condition survey / specification-level output, use a specialist inspection.
What if we can’t access flats for annual checks?
Treat access like a process: schedule visits, communicate with residents, log attempts, and record outcomes. “Best endeavours” is usually evidenced by a clear audit trail of attempted access.
Do existing flat entrance doors have to meet today’s standards for new doors?
Not automatically. Guidance generally focuses on ensuring doors are fit for purpose, undamaged, and functioning as intended. For replacement decisions, align to the building’s risk profile and competent advice.
Do we need photos for every door, every time?
No. Photos are most useful where they add clarity: damage, missing seals, poor fit, or when evidence is needed for close-out and dispute resolution.
Related pages
Note
This article is general information and isn’t legal advice. Always align checks and remedials to the building’s fire risk assessment and competent guidance.